Originator: |
|
NHS Improvement Estates and Facilities
|
|
|
|
- Care Trusts
- Mental Health Trusts
- Specialists Trusts
- NHS Regional Offices
- Learning Disabilities Trusts
- Mental Health & Social Care Trusts
- Ambulance Trusts
- Acute Trusts
- Community Trusts
|
|
|
- Independent Healthcare Providers (registered with CAS)
- Clinical Commissioning Groups
- Social Care Providers (registered with CAS)
|
Title: |
|
Vernacare Vortex macerator: potential to contamination mains water supply.
|
Broadcast content: |
|
We have been informed that Vernacare Vortex Macerators, supplied under WRAS approval number 1309094, do not comply with the requirements of the UK Water Supply (Water Fittings) Regulations (Byelaws in Scotland). A polythene silencer tube fitted to the water tank inlet float valve means that the air gap is not maintained between the water tank contents and the mains water supply thereby creating the potential for contamination of the mains water supply by the tank contents.
|
Additional information: |
|
NHS Regional Offices: please cascade to GP and Dental practices.
|
Action underway deadline: |
|
23-Oct-2018
|
Action complete deadline: |
|
29-Mar-2019
|